Mould Risk on Wall Surface in Partly Underground Technical Room

but.event.date25.01.2024cs
but.event.titleJuniorstav 2024cs
dc.contributor.authorNováková, Iva
dc.contributor.authorŠikula, Ondřej
dc.date.accessioned2024-05-07T08:53:24Z
dc.date.available2024-05-07T08:53:24Z
dc.date.issued2024-05-07cs
dc.description.abstractThis conference article aims at the indoor climate in the technical room of an underground water reservoir. This indoor climate is specific by high relative humidity (average 75.2% r.h.) and low air temperature (average 13.6 °C). Therefore, this research study focuses on surface condensation and mould risk on the partly underground wall in the technical room. The experimental research combines long-term monitoring (22 months). Long-term of indoor climate and thermal numerical simulation. The experimental measurement shows condensation risk on the indoor wall surface, and the unsteady 2D numerical simulation in software Calculation Area 4.0e shows temperature fluctuation on indoor wall surfaces. Finally, the empirical VVT model predicts mould risk on the indoor wall surface for the over-terrain part in autumn and summer for the under-terrain part. en
dc.formattextcs
dc.format.extent1-9cs
dc.format.mimetypeapplication/pdfen
dc.identifier.citationJuniorstav 2024: Proceedings 26th International Scientific Conference Of Civil Engineering, s. 1-9. ISBN 978-80-86433-83-7.cs
dc.identifier.doi10.13164/juniorstav.2024.24035en
dc.identifier.isbn978-80-86433-83-7
dc.identifier.urihttps://hdl.handle.net/11012/245453
dc.language.isoencs
dc.publisherVysoké učení technické v Brně,Fakulta stavebnícs
dc.relation.ispartofJuniorstav 2024: Proceedings 26th International Scientific Conference Of Civil Engineeringcs
dc.relation.urihttps://juniorstav.fce.vutbr.cz/proceedings2024/
dc.rights© Vysoké učení technické v Brně,Fakulta stavebnícs
dc.rights.accessopenAccessen
dc.subjectWater reservoiren
dc.subjectexperimental measurementen
dc.subjectnumerical simulationen
dc.subjecthigh relative humidityen
dc.subjectmould risk en
dc.titleMould Risk on Wall Surface in Partly Underground Technical Roomen
dc.type.driverconferenceObjecten
dc.type.statusPeer-revieweden
dc.type.versionpublishedVersionen
eprints.affiliatedInstitution.departmentFakulta stavebnícs
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
juniorstav-2024-24035.pdf
Size:
1017.74 KB
Format:
Adobe Portable Document Format
Description:
Collections