Axial Channel Effect on Leakage Reactance in Split-Winding Transformer.

but.event.date26.04.2022cs
but.event.titleSTUDENT EEICT 2022cs
dc.contributor.authorMrajca, M.
dc.contributor.authorCipín, R.
dc.date.accessioned2023-04-25T10:17:09Z
dc.date.available2023-04-25T10:17:09Z
dc.date.issued2022cs
dc.description.abstractTransformer short-circuit impedance is one of the most important output parameters in the design process. Its value depends mainly on leakage inductance, which is different for one or both shorted output windings during short-circuit test of split-winding transformer with input windings working in parallel. In this paper, an analysis of split-winding transformer with changing axial channel between winding pairs and its effect on leakage reactance has been performed for both shorted outputs. The effect is evaluated with analytical calculations, 3D and 2D finite element method simulations on a typical 5300 kVA three-phase oil transformer. The results show that the channel can’t be neglected in short-circuit calculation and the geometry of the transformer can be simplified to 2D with minimal influence on results.en
dc.formattextcs
dc.format.extent331-335cs
dc.format.mimetypeapplication/pdfen
dc.identifier.citationProceedings I of the 28st Conference STUDENT EEICT 2022: General papers. s. 331-335. ISBN 978-80-214-6029-4cs
dc.identifier.isbn978-80-214-6029-4
dc.identifier.urihttp://hdl.handle.net/11012/209359
dc.language.isoencs
dc.publisherVysoké učení technické v Brně, Fakulta elektrotechniky a komunikačních technologiícs
dc.relation.ispartofProceedings I of the 28st Conference STUDENT EEICT 2022: General papersen
dc.relation.urihttps://conf.feec.vutbr.cz/eeict/index/pages/view/ke_stazenics
dc.rights© Vysoké učení technické v Brně, Fakulta elektrotechniky a komunikačních technologiícs
dc.rights.accessopenAccessen
dc.subjectsplit-winding transformeren
dc.subjectleakage inductanceen
dc.subjectshort-circuit impedanceen
dc.subjectaxial channelen
dc.subjectfinite element methoden
dc.subjectFEMen
dc.subjectsimulationen
dc.subjectanalytical calculationen
dc.titleAxial Channel Effect on Leakage Reactance in Split-Winding Transformer.en
dc.type.driverconferenceObjecten
dc.type.statusPeer-revieweden
dc.type.versionpublishedVersionen
eprints.affiliatedInstitution.departmentFakulta elektrotechniky a komunikačních technologiícs