Utilization of an Air-PCM Heat Exchanger in Passive Cooling of Buildings: A Simulation Study on the Energy Saving Potential in Different European Climates

Loading...
Thumbnail Image

Authors

Charvát, Pavel
Klimeš, Lubomír
Zálešák, Martin

Advisor

Referee

Mark

Journal Title

Journal ISSN

Volume Title

Publisher

MDPI
Altmetrics

Abstract

The energy saving potential (ESP) of passive cooling of buildings with the use of an air-PCM heat exchanger (cold storage unit) was investigated through numerical simulations. One of the goals of the study was to identify the phase change temperature of a PCM that would provide the highest energy saving potential under the specific climate and operating conditions. The considered air-PCM heat exchanger contained 100 aluminum panels filled with a PCM. The PCM had a thermal storage capacity of 200 kJ/kg in the phase change temperature range of 4 °C. The air-PCM heat exchanger was used to cool down the outdoor air supplied to a building during the day, and the heat accumulated in the PCM was rejected to the outdoors at night. The simulations were conducted for 16 locations in Europe with the investigated time period from 1 May–30 September. The outdoor temperature set point of 20 °C was used for the utilization of stored cold. In the case of the location with the highest ESP, the scenarios with the temperature set point and without the set point (which provides maximum theoretical ESP) were compared under various air flow rates. The average utilization rate of the heat of fusion did not exceed 50% in any of the investigated scenarios.
The energy saving potential (ESP) of passive cooling of buildings with the use of an air-PCM heat exchanger (cold storage unit) was investigated through numerical simulations. One of the goals of the study was to identify the phase change temperature of a PCM that would provide the highest energy saving potential under the specific climate and operating conditions. The considered air-PCM heat exchanger contained 100 aluminum panels filled with a PCM. The PCM had a thermal storage capacity of 200 kJ/kg in the phase change temperature range of 4 °C. The air-PCM heat exchanger was used to cool down the outdoor air supplied to a building during the day, and the heat accumulated in the PCM was rejected to the outdoors at night. The simulations were conducted for 16 locations in Europe with the investigated time period from 1 May–30 September. The outdoor temperature set point of 20 °C was used for the utilization of stored cold. In the case of the location with the highest ESP, the scenarios with the temperature set point and without the set point (which provides maximum theoretical ESP) were compared under various air flow rates. The average utilization rate of the heat of fusion did not exceed 50% in any of the investigated scenarios.

Description

Citation

Energies. 2019, vol. 12, issue 6, p. 1-17.
https://www.mdpi.com/1996-1073/12/6/1133

Document type

Peer-reviewed

Document version

Published version

Date of access to the full text

Language of document

en

Study field

Comittee

Date of acceptance

Defence

Result of defence

Endorsement

Review

Supplemented By

Referenced By

Creative Commons license

Except where otherwised noted, this item's license is described as Creative Commons Attribution 4.0 International
Citace PRO