Heat storage efficiency and effective thermal output: Indicators of thermal response and output of radiant heating and cooling systems

Loading...
Thumbnail Image

Authors

Krajčík, Michal
Šikula, Ondřej

Advisor

Referee

Mark

Journal Title

Journal ISSN

Volume Title

Publisher

Elsevier
Altmetrics

Abstract

An alternative indicator of thermal response of radiant heating and cooling systems called heat storage efficiency (HSE) has been tested. The heat storage efficiency was compared with established indicators represented by the time constant tau(63), response time tau(95), and thermal energy stored (TES). The comparison was performed for three wall cooling systems with various combinations of pipe location, configuration of material layers, and materials of the thermal core. Considering the whole response curve (HSE) instead of focusing on one specific point on the curve (tau(63), tau(95)) allowed comparing the thermal response of complex systems by a single value. It also permitted predicting thermal response consistently regardless of the system and core material. Thermal energy stored predicted the thermal response of certain systems, but it may not be suitable for comparing the thermal response of radiant systems with different thermal admittance. Besides, a novel indicator of thermal output called effective thermal output (ETO) has been proposed. The effective thermal output considers both the steady-state thermal performance represented by the nominal thermal output and dynamic thermal performance represented by the heat storage efficiency. For thermally active building systems (TABS), effective thermal output was up to 57% lower than the nominal thermal output. (C) 2020 Elsevier B.V. All rights reserved.
An alternative indicator of thermal response of radiant heating and cooling systems called heat storage efficiency (HSE) has been tested. The heat storage efficiency was compared with established indicators represented by the time constant tau(63), response time tau(95), and thermal energy stored (TES). The comparison was performed for three wall cooling systems with various combinations of pipe location, configuration of material layers, and materials of the thermal core. Considering the whole response curve (HSE) instead of focusing on one specific point on the curve (tau(63), tau(95)) allowed comparing the thermal response of complex systems by a single value. It also permitted predicting thermal response consistently regardless of the system and core material. Thermal energy stored predicted the thermal response of certain systems, but it may not be suitable for comparing the thermal response of radiant systems with different thermal admittance. Besides, a novel indicator of thermal output called effective thermal output (ETO) has been proposed. The effective thermal output considers both the steady-state thermal performance represented by the nominal thermal output and dynamic thermal performance represented by the heat storage efficiency. For thermally active building systems (TABS), effective thermal output was up to 57% lower than the nominal thermal output. (C) 2020 Elsevier B.V. All rights reserved.

Description

Citation

ENERGY AND BUILDINGS. 2020, vol. 229, issue 1, p. 1-14.
https://www.sciencedirect.com/science/article/pii/S037877882031937X

Document type

Peer-reviewed

Document version

Accepted version

Date of access to the full text

Language of document

en

Study field

Comittee

Date of acceptance

Defence

Result of defence

Endorsement

Review

Supplemented By

Referenced By

Creative Commons license

Except where otherwised noted, this item's license is described as Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International